The air ratio can be determined from the concentrations of the flue gas components CO, CO2 and O2, the correlations are shown in the so-called combustion chart (see image right). When there is ideal mixing of fuel and air, any CO2 content is related to a specific CO content (in the range λ2 content (in the range λ>1). The CO2 value on its own is not clear due to the curve profile running beyond a maximum, which means that an additional test is required to establish whether the gas also contains CO or O2 in addition to the CO2. For operation with excess air (i.e. normal scenario), a definitive measurement of O2 is now generally preferred. The curve progressions are fuel-specific, i.e. each fuel has its own diagram and a specific value for CO2 max. The connections between these numerous diagrams is often summarized in an easy-to-handle nomogramm (“fire triangle”, not illustrated here). This can be applied to any type of fuel.

The following two formula apply roughly to the theoretical calculation of the air ratio from the CO2 or O2 readings:

  • CO2 max: Fuel-specific maximum CO2 value. If required, this value can be determined by Testo as a service. If required, this value can be determined by Testo as a service.

  • CO2 and O2: Measured (or calculated) values in the flue gas

Energy balance of a combustion plant

In stationary operating mode, the sum of all the energies supplied to the plant must be equal to the sum of the energies delivered by the plant; see this table :

Supplied energiesDischarged energies
Net calorific value and tangible fuel energyTangible heat and chemically bound energy of flue gases (flue gas loss)
Tangible heat of combustion airTangible heat and net calorific value of fuel residues in ash and slag
Thermal equivalent of the mechanical energy converted in the plantSurface losses as a result of heat conduction
Heat brought in through the productHeat dissipated with the product Convection losses as a result of furnace leaks

The main contribution to the loss is the flue gas loss. It is a function of the difference between the flue gas temperature and combustion air temperature, the O2 or CO2 concentration in the flue gas and fuel-specific factors. In condensing boilers, this flue gas loss is reduced in two ways – via utilization of the condensation heat and via the resultant lower flue gas temperature. The flue gas loss can be calculated using the following formulae:

FT: Flue gas temperature

AT: Combustion air temperature

A2, B: Fuel-specific factors (see table)

21: Oxygen content in the air

O2: Measured O2 concentration

KK: Variable which shows the variable qA as a minus value if the dewpoint is undershot. Required for measurement on condensing systems.

For solid fuels, factors A2 and B equal zero. In that case, using the factor f, the formula is simplified to create the so-called Siegert formula:

FT: Flue gas temperature

AT: Combustion air temperature

CO2: Measured CO2 concentration