  1. Operation independent of measuring location and display of readings via smartphone or tablet and the testo 330i App
  2. Paperless documentation and report creation on site with the testo 330i App
  3. Reliable attachment of the flue gas probe with the testoFix probe holder
  4. Practical accessories, including probes and temperature probe
  5. Everything you need to carry out efficient servicing and commissioning of heating systems using the testo 330i flue gas analyzer – in one compact set.
    The testo 330i flue gas analyzer combines the proven measuring technology of the preceding model testo 330 LL with a revolutionary new method of operation: operation independent of measuring location via smartphone, a sturdy testoFix probe holder and paperless documentation. This instrument embodies the current trends in flue gas measurement.
    The centrepiece of the set is the testo 330i flue gas analyzer with H2-compensated CO sensor. The flue gas analyzer is therefore also approved for the official acceptance testing of heating systems.
    Operation of the flue gas analyzer and the display of readings are implemented independently of the measuring location via the testo 330i App on your smartphone or tablet. Here, you can make adjustments to the measuring instrument, analyze the flue gas values, enter customer data and create measurement protocols. You can then add comments or photos of the system to the protocols, and send them to the customer or your office via e-mail.

    Requirement: iOS 7.1 / Android 4.3 or newer. Mobile end device with Bluetooth 4.0.

    The testo 330i flue gas analyzer also has the following impressive features

    • User-replaceable long-life sensors with a service life of up to 6 years. This saves at least one sensor replacement over the flue gas analyzer's typical useful life
    • TÜV-tested according to 1st German Federal Immission Control Ordinance (BImSchV) and EN 50379, Parts 1-3
    • Integrated draught and gas zeroing without removing the probe. The probe can remain in the flue during zeroing
    • Fresh air dilution upon exceeding a CO threshold value up to 30,000 ppm
    • Fully enclosed, particularly robust plastic housing
    Also included in the set: a modular flue gas sampling probe (180 mm) with a 65 cm long, extra-flexible hose and a 190 mm long combustion air temperature probe.
    The testoFix probe holder is included in the set, which enables the probes to be securely attached to the flue gas duct quickly and easily. This global innovation also serves as a fall-proof suspension system for the testo 330i flue gas analyzer. A mains unit and the practical system case, in which all set components can be stowed away compactly and safely, complete this set.

    •    testo 330i with H2-compensated CO sensor 0632 3000 51
    •    Modular flue gas probe with hose (650 mm) 0600 9780
    •    Combustion air temperature probe (190 mm) 0600 9787
    •    International mains unit 0554 1096
    •    testoFix probe holder for probes with a diameter of 8 mm (0554 3006)
    •    Instrument case for testo 330i, probes and accessories (dimensions: 520 × 130 × 400 mm, WxHxD) 0516 3302

     

    General technical data

    Weight
    720 g (excluding battery)
    Dimensions
    270 x 160 x 57 mm
    Operating temperature
    -5 to +45 °C
    Power supply
    Rech. batt. block 3.7 V / 2.6 Ah; Mains unit 6 V / 1.2 A (optional)
    System requirements
    requires iOS 7.1 or newer; requires Android 4.3 or newer; requires mobile end device with Bluetooth 4.0
    Maximum memory
    500000 readings
    Storage temperature
    -20 to +50 °C

    Differential Pressure - Piezoresistive

    Measuring range
    0 to 300 hPa
    Accuracy
    ±1.5 % of mv (Remaining Range)
    ±1 % of mv (+50.1 to +100.0 hPa)
    ±0.5 hPa (0.0 to +50.0 hPa)
    Resolution
    0.1 hPa

    Flue gas O₂

    Measuring range
    0 to 21 Vol.%
    Accuracy
    ±0.2 Vol.%
    Resolution
    0.1 Vol.%

    Accessories for probes

    Combustion air / temperature

    Probes

  6. Probes
    Flue gas probe 180mm, 8mm
    Flue gas probe 180 mm, diameter 8 mm
      :
      0600 9780
      SAR 1 058
    • Probes
      Flue gas probe 300mm, 8mm
      Flue gas probe 300 mm, diameter 8 mm
        :
        0600 9781
        SAR 1 121
      • Probes
        Flue gas probe 180mm, 6mm
        Flue gas probe 180 mm, diameter 6 mm
          :
          0600 9782
          SAR 1 058
        • Probes
          Flue gas probe 300mm, 6mm
          Flue gas probe 300 mm, diameter 6 mm
            :
            0600 9783
            SAR 1 121
          • Accessories

            Accessories for measuring instrument

          • Accessories for measuring instrument
            Smoke tester with oil and soot sheet, for measuring soot in flue gas, excl. cone (part no. 0554 9010)
              :
              0554 0307
              SAR 597
            • Accessories for measuring instrument
              Spare particle filter
              Spare dirt filters - for probe handle (10 off)
                :
                0554 3385
                SAR 119
              • Flue gas analysis and flue gas measurement

                At the core of the measuring technology of the testo 330i are the two long-life sensors for measuring O2 and CO. An NO sensor is optionally available. With the testo 330i, flue gas and draught are measured in parallel – therefore you always have an overview of all relevant readings on a screen in the testo 330i App.

                Differential pressure measurement

                You can also use the testo 330i flue gas analyzer to measure the gas supply on gas boilers. Measure the gas flow and gas resting pressure to ensure that a gas boiler can be commissioned properly. In conjunction with the manufacturer's specifications concerning the nozzle pressure, the results of this measurement will enable you to tailor the output of the boiler to the home's actual heat requirement.

                O2 supply air measurement

                In balanced flue systems, you can use the testo 330i to find out whether there is a leak in the flue gas system. For this, simply measure the O2 content of the combustion air in the dual wall clearance. This way, you can ensure that no flue gas is getting into the combustion air supply. This prevents damage due to condensate or impairment of the combustion process.

                • Testo ZIV driver in the 2000 version. The Testo ZIV driver is used to connect the testo 320 and testo 330 measuring instruments to an application program (sweeping district administration program) according to the interface Version 2.0 defined by the Zentralverband des Schornsteinfegerhandwerks (Central Association of Chimney Sweeps, ZIV). Please check with the manufacturer of your application program as to whether this interface is supported. If Microsoft .NET Framework 4.0 has not been installed on the computer, it must be downloaded from the Microsoft website and installed on the system.
                • The Testo ZIV driver is used to connect the testo 300, testo 320 and testo 330 measuring instruments to an application program (sweeping district administration program) according to the interface defined by the Zentralverband des Schornsteinfegerhandwerks (ZIV, Central Association of Chimney Sweeps) in version 1.0 of 01. August 2012, in version 2.0 of 13. February 2017 as well as version 3.0 from 02. July 2021. Please check with the manufacturer of your application program as to whether this interface is supported.
                • Firmware testo 330i(v2.11, 3.56 MB)
                  If the firmware update does not start under Windows 8.1 or Windows 10, a new bootloader must be installed on the measuring device once.
                  A description and all necessary files can be found under the search term: Update-Kit / Bootloader
                • Update-Kit / Bootloader(V1.22, 1.24 MB)
                  (testo 330 LL | testo 330i | testo 350 Control Unit + Analysis Box | testo 320)
                  If the firmware update does not start under Windows 8.1 or Windows 10, a new bootloader must be installed on the measuring device once.