1. Home
    2. Vane measurement probe Ø 100 mm, for measurements on ventila...

    Vane/temperature probe (Ø 100 mm) - for air outlets

    0635 9343
  1. Vane diameter: 100 mm 
  2. Integrated temperature measurement up to +60 °C
  3. Intelligent calibration concept
  4. Flow measuring range: +0.1 to +15 m/s
  5. Product no longer available. Have you checked out its successor?
    Why not enjoy the benefits that it has to offer:
    >> To the product (fixed cable)
    >> To the product (wireless, with Bluetooth)
    Please note that the successor products are only compatible with testo 400 or testo 440.
    Use the 100 mm vane/temperature probe to determine flow velocity and volume flow at ventilation outlets. Integrated temperature measurement enables the vane anemometer to measure temperatures up to +60 °C.
    For convenient, accurate measurements at plate outlets and ventilation grilles, we recommend that you use the vane/temperature probe in conjunction with the testo 480 measuring instrument and the testovent 417 funnel set (both optionally available). This guarantees simple testing of incoming/outgoing air – such as in the controlled ventilation of living spaces.

    If you add in the testovent 417 volume flow straightener (optional), you can achieve an impressively high level of precision when carrying out measurements at swirl outlets.

    The optional telescope with ball head makes it easier to measure flow velocities at ceiling outlets, for example. The telescope is 1.8 m long when extended.

    Intelligent calibration concept

    The probe offers maximum digital measurement reliability. The digital probe allows readings to be processed directly in the probe. This technology eliminates instrument measurement uncertainty. The probe can be returned on its own (without the measuring instrument) for calibration. Calculating the determined calibration data in the probe generates a zero-error display.

    Vane/temperature probe (Ø 100 mm).

    Note: you need a plug-in head cable (0430 0100) for this probe.

    General technical data

    Diameter
    100 mm

    Temperature - NTC

    Measuring range
    0 to +60 °C
    Accuracy
    ±0.5 °C
    Resolution
    0.1 °C

    Velocity / Volume flow

    Measuring range
    +0.1 to +15 m/s
    Accuracy
    ±(0.1 m/s + 1.5 % of mv)
    Resolution
    0.01 m/s