Carry out measurements without any annoying cables: use the kit to handle all relevant measurements in ventilation ducts and at air/ceiling outlets. You will receive the testo 440 dP air velocity and IAQ measuring instrument including differential pressure sensor, two vane probe heads (Ø 100 mm and Ø 16 mm) and a humidity/temperature probe head – all three can be attached to the universal Bluetooth® handle supplied. To make measurements more convenient, both vane probe heads can be combined with the telescope included in the kit. The equipment can be transported safely and conveniently in the robust case.
Registracija izdelka
Z registracijo svojega izdelka vam podaljšamo običajno garancijo proizvajalca za leto dni.
Measuring range | −40 to +150 °C |
---|---|
Accuracy | ±0,4 °C (+75 to +99,9 °C) ±0,4 °C (−40 to −25,1 °C) ±0,5 % of mv (Remaining Range) ±0,3 °C (−25 to +74,9 °C) |
Resolution | 0,1 °C |
Measuring range | −200 to +1370 °C |
---|---|
Accuracy | ±(0,3 °C + 0,3 % of mv) |
Resolution | 0,1 °C |
Measuring range | −150 to +150 hPa |
---|---|
Accuracy | ±0,05 hPa (0 to 1,00 hPa) (1,01 to +150 hPa) ±0,2 hPa + 1,5 % of mv |
Resolution | 0,01 hPa |
Weight | 250 g |
---|---|
Dimensions | 154 x 65 x 32 mm |
Operating temperature | −20 to +50 °C |
Connectable probes | 1 x digital probe with cable or 1 x Temperature NTC TUC, 1 x digital Bluetooth probe or testo Smart Probe, 1 x differential pressure (internal), 1 x Temperature TC Type K |
Product colour | black/orange |
Battery type | 3 AA mignon 1.5 V |
Battery life | 12 h (typically vane measurement) |
Interface | Bluetooth®; USB |
Storage temperature | −20 to +50 °C |
Storage temperature | −20 to +60 °C |
---|---|
Weight | 360 g |
Dimensions | 375 x 105 x 46 mm |
Operating temperature | −5 to +50 °C |
Probe head diameter | 100 mm |
Product colour | black/orange |
Battery type | 4 x type AA batteries |
Battery life | 60 h |
Data transfer | Bluetooth® |
Radio range | 20 m |
Measuring range | −20 to +70 °C |
---|---|
Accuracy | ±0,5 °C |
Resolution | 0,1 °C |
Measuring range | 0,3 to 35 m/s |
---|---|
Accuracy | ±(0,2 m/s + 1,5 % of mv) (20,01 to 35 m/s) ±(0,1 m/s + 1,5 % of mv) (0,3 to 20 m/s) |
Resolution | 0,01 m/s |
Measuring range | −10 to +70 °C |
---|---|
Accuracy | ±1,8 °C |
Resolution | 0,1 °C |
Measuring range | 0,6 to 50 m/s |
---|---|
Accuracy | ±(0,2 m/s + 1 % of mv) (0,6 to +40 m/s) ±(0,2 m/s + 2 % of mv) (40,1 to 50 m/s) |
Resolution | 0,1 m/s |
Storage temperature | -10 to +70 °C |
---|---|
Weight | 60 g |
Dimensions | 245 x 16 x 16 mm |
Operating temperature | -10 to +70 °C |
Length probe shaft | 230 mm |
Diameter probe shaft | 16 mm |
Probe head diameter | 16 mm |
Product colour | Black |
Measuring range | −20 to +70 °C |
---|---|
Accuracy | ±0,5 °C |
Resolution | 0,1 °C |
Measuring range | 0 to 100 %RH |
---|---|
Accuracy | long-term stability: ±1 %RH / year ±0,03 %RH/K (k=1) ±2 %RH (5 to 90 %RH) |
Resolution | 0,1 %RH |
Storage temperature | −20 to +70 °C |
---|---|
Weight | 30 g |
Dimensions | 160 x 28 x 28 mm |
Operating temperature | −20 to +70 °C |
Diameter probe shaft | 12 mm |
Length probe shaft | 140 mm |
Product colour | Black |
Weight | 155 g |
---|---|
Dimensions | angle: 65 x 65 x 15 mm telescope: 375 x 17 x 16 mm |
Operating temperature | −5 to +50 °C |
Length telescope | 1.000 mm |
Diameter telescope | 12 mm |
Product colour | Black |
Storage temperature | −20 to +60 °C |
Weight | 1400 g |
---|---|
Dimensions | 516 x 135 x 256 mm |
Product colour | Black |