Between rooms of different cleanroom classes, pressure differences between 5 and 20 Pa must be ensured from cleaner room to less clean room. The minimal positive pressure of the cleanroom ensures that no air flows back into the cleaner area from the unclean area when doors are opened. The lowest contamination-level cleanroom itself is also accessed via airlocks for personnel and materials, where strong air currents stir up the particles present and extract them via filter systems. According to DIN EN ISO 14644-3, the pressure difference of a cleanroom to the personnel and material airlocks, to any cleanrooms of other purity classes as well as to the surroundings, must be tested. A test of differential pressure at the filter should also be carried out.
Measurement of differential pressure requires highly precise measurement technology
Measurement of differential pressure between rooms and at the filter
The testo Smart App guides you quickly and easily through measurements on refrigeration, air conditioning and heating systems.
Now new:
PRO measuring programs for increasing the efficiency of your applications
Multifunctional
Compatible with all Bluetooth-enabled Testo measuring instruments
Efficient
Direct report dispatch by e-mail
Fast
All measurement values at a glance
Easy
Intuitive measurement menus
Clever
Free download, free use
NEW
PRO measuring programs